Complete the following entries in the service log:
Name of the executing body (company, department)
Names of the staff on duty
Identification of the device/system (type, serial number, inventory
number) and the respective accessories
Completed inspections and readings
Scope and results of the inspections
Measuring method, measuring device, measuring results for
readings
Overall assessment
Date and signature of the assessing person; personal coding is a
viable alternative for IT applications.
8.2.3 Check sealing function of plug
To be performedby professional electrician
Check sealing function of DIN-8 plug
1 Separate the device from the energy supply.
2 Check sealing O-ring (3) of the DIN-8 plug (2) for damage.
3 Ensure that there is no irregular gap between the DIN-8 plug (2)
and the connection outlet (1) of the housing.
4 If sealing O-rings (3) are damaged, have the manufacturer
replace them.
5 If there is no damage, reconnect the device with the energy
supply.
1
3
2
Fig. 56
Service log
73