6.1 Installation location
Adhere to the technical data in accordance with operating condi-
tions († chapter 11 Appendix).
• Install in a location where the actuator is not exposed to strong
UV radiation or corrosive or explosive air media.
6.2 Inspections prior to first
operation
• Execution by professional electrician
Prior to the first operation, a professional electrician must perform
and document the following tests and readings:
• Check visual condition
• Function check of operating features and safety features
• Reading of protective conductor resistance
• Reading of leakage currents
• Reading of insulation resistance
Special precaution regarding EMC
The device requires special precautions regarding EMC and must
be installed and put into service according to the EMC informa-
tion provide in this operating manual († Safety, Chapter 2.8)
WARNING
!
Note!
Additional information concerning inspections and
readings († Chapter Maintenance).
Crush hazard
Risk of damage to the linear actuator MAX caused by static and
dynamic overload. Do not use the actuator beyond the permis-
sible operating data.
• Note the maximum permissible operating data in the
datasheet.
• Note the product label of the actuator (end warning box)
WARNING
39