7.7 Settings and adjustments BSS-12030
7.7.1 Disabling the indicator lights
The unit has connections for 10 sensors. The indicator LEDs corresponding to the unconnected sensor posi-
tions are lit up continuously. This can be prevented by removing the electronic module’s corresponding jump-
ers J1 - J10. The jumpers only affect the operation of the LED indicator and not the relay.
7.7.2 Adjusting the sensors' switching point
The alarm limit for float movement can be adjusted by moving the sensor up or down in its holder. When the
sensor is locked in place, make sure that the sensor is tightly against the flow tube, i.e. there is no gap be-
tween the tube and the sensor.