62
8.5 Settings and adjustments BSC-051015
8.5.1 Setting the delay
The delay is set on the electronic card in field J1 by setting the jumper at the desired position 10, 50 or 100
(s). If both 10 s and 50 s positions are closed, the delay is 0 s.
8.5.2 Adjusting the sensors' switching point
The alarm limit for float movement can be adjusted by moving the sensor up or down in its holder. Fig. 24,
sensitivity adjustment for alarm sensors shows the switching points with three different adjustment set-
tings.
8.6 Settings and adjustments BSC-12030
8.6.1 Setting the delay
The delay is set on the electronic card in field J1 by setting the jumper at the desired position 10, 50 or 100
(s). If both 10 s and 50 s positions are closed, the delay is 0 s.
8.6.2 Adjusting the sensors' switching point
The alarm limit for float movement can be adjusted by moving the sensor up or down in its holder. When the
sensor is locked in place, make sure that the sensor is tightly against the flow tube, i.e. there is no gap be-
tween the tube and the sensor.