EasyManua.ls Logo

Skope ReFlex Underbench - Page 22

Skope ReFlex Underbench
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
Electronic Controller
Service Manual
SKOPE Reflex Underbench Fridge and Freezer
27
Probe failure
A probe other than the control
probe has failed. The cabinet
will continue to operate with
partial function but requires
service.
Cartridge swap is not required.
Evaporator probe or
connections
Either:
Measure the probe resistance to make sure it
is within the range.
Compare the probe’s temperature with the
known temperature, using an external trusted
thermometer.
Replace the probe if required.
Controller
The controller may be reading incorrectly and
need replacing.
28
No downward tendency
The temperature is no longer
decreasing.
Blocked condenser
Remove and clean the condenser filter.
Check that the condenser is free of debris.
If the coil is dirty, clean it with a vacuum cleaner or
soft brush.
Poor installation or ventilation Check the installation guidelines.
Cartridge or cabinet gasket
seals leaking
Check that the gasket is intact and not broken and
leaking. If required, replace the door gasket.
Ensure the installation levers are lifting the
cartridge up onto the case correctly.
Door not self-closing or door
gasket leaking
Open the door and let it go. If it does not close on
its own, repair the self-closing mechanism.
If required, replace the door gasket.
Product blocking cabinet airflow
Check if the return air grille is covered by product.
If so, move the product from the grille and
observe.
Compressor is overloaded from
excess door openings or
ambient temperature
Ensure that the cabinet is operating in its climate
class.
Condenser or evaporator fan
motor or blade
Inspect the condenser and evaporator fans safely,
and replace if faulty.
Controller
The controller may be reading incorrectly and
need replacing.
Compressor or gas leak Swap the cartridge.
29
Compressor cutting out
The compressor cut out on its
internal protection or pressure
switch.
Blocked condenser
Remove and clean the condenser filter.
Check that the condenser is free of debris.
If the coil is dirty, clean it with a vacuum cleaner or
soft brush
Poor installation or ventilation Check the installation guidelines.
Cabinet, door, or cartridge
gasket leaking
Check that the gasket is intact and not broken and
leaking. If required, replace the door gasket.
Ensure the installation levers are lifting the
cartridge up onto the case correctly.
Product blocking cabinet airflow
Check if the return air grille is covered by product.
If so, move the product from the grille and
observe.
Compressor is overloaded from
excess door openings or
ambient temperature
Ensure that the cabinet is operating in its climate
class.
Condenser or evaporator fan
motor or blade
Inspect the condenser and evaporator fans safely,
and replace if faulty.
Controller
The controller may be reading incorrectly and
need replacing.
Compressor or gas leak Swap the cartridge.
Table 6: Alarms (continued)
Code Description Possible root cause Action

Related product manuals