SKOPE Reflex Underbench Fridge and Freezer
Troubleshooting and Diagnostics
Service Manual
Evaporator probe fault Replace the evaporator probe.
Frozen evaporator
coil
Setpoint is too cold Check and raise the setpoint.
Controller fault Replace the controller.
Short of refrigerant
Perform refrigeration system diagnostics and service as
required.
Ice build-up inside
evaporator box
Leaking cartridge seal
Check that the evaporator tub seals are fully clamped,
and the cabinet top seal is good without gaps. Micro-gaps
will allow ice build-up in the cabinet.
Cabinet door is opened too often Ensure the door is closed more often.
Power
consumption is
higher than
expected
Cartridge is operating too hot
Clean the condenser.
Ensure the cabinet has good ventilation around the
refrigeration cartridge.
Ensure the cabinet is within the maximum operating
temperature.
Product is too cold Raise the setpoint.
Door not closing properly Check and clean the door gasket.
Excessive door opening Limit door openings.
Electronic controller is in “Night” mode
Change the cabinet into “Day” mode by pressing and
holding the light button on the electronic controller
faceplate, or holding the door open for ten seconds.
Refrigeration system error (no active
fault alarm)
Check the SCS Connect Field app statistics to see if and
when the controller signalled a fault or alarm.
Product is too
warm
Cartridge is operating too hot
Excessive refrigeration heat load
Ensure the cabinet has good ventilation around the
refrigeration cartridge.
Ensure the cabinet is within the maximum operating
conditions.
Setpoint is too high Lower the setpoint.
Recently loaded Allow the product time.
Cabinet is overstocked
Remove some product.
Product must not overhang the shelves.
Refrigeration system error (indicated by
the electronic controller)
Diagnose and repair. If a system fault is found contact
SKOPE for information on how to proceed.
Frequent door opening Limit door openings.
Door not closing properly Check and clean the door gasket.
Moisture build up
on cabinet exterior
High humidity
Check the ambient operating temperature and reposition
the cabinet if necessary.
Cabinet door does
not close properly
Cabinet is on an uneven surface Level the cabinet.
Door is obstructed Check the shelves and product.
Door gasket is dirty Check and clean the door gasket.
Warm cabinet
temperatures
Compressor
operating for long
periods (more
than 1 hour)
Blocked condenser coil Clean the condenser coil.
Poor ventilation around refrigeration
cartridge
Ensure the cabinet has good ventilation around the
refrigeration cartridge.
Ensure the cabinet is within the maximum operating
temperature.
Table 14: Cabinet and cartridge troubleshooting (continued)
Problem Possible Cause Recommended Action