HGMS62 Split Type Genset Controller User Manual Page 26 of 58
Time from mains abnormal or remote
start signal active to genset start.
Time from mains normal or remote start
signal inactive to genset stop.
Pre-power time of heater plug before
starter is powered.
Every starter power-on time.
Wait time before secondary power-on
begins when engine crank fails.
Low oil pressure, high temperature,
under speed, under frequency, under
voltage, charge failure alarms are
inactive during the period.
Genset idle running time when starting.
Warming up time before closing after
genset entering high-speed running.
Cooling time before stopping after
genset off-load.
Genset idle running time when stopping.
Stop solenoid power-on time when
stopping.
Time from idle delay over to stop
completely when “ETS Time” is 0; Time
from ETS delay over to stop completely
when “ETS Time” is not 0.
Time from complete stop to standby.
Raise speed pulse output time when
genset entering warming up.
Drop speed pulse output time when
genset entering stop idle.
0: Temperature Sensor; 1: Aux. Sensor 1;
2: Aux. Sensor 2; 3: Oil Pressure Sensor;
4: Fuel Level Sensor.
Pre-fuel output time before starter is
powered on.