HGMS62 Split Type Genset Controller User Manual Page 32 of 58
Controller address in remote monitoring.
0: Simplified Chinese; 1: English; 2:
Others.
The password for entering advanced
parameter setting.
LCD is always illuminated when it is 0.
0: 4 parameters 1: 8 parameters
Display time of master control module:
YY:MM:DD (WEEK); HH:MM:SS.
Schedule and Maintenance Setting
0: Warning; 1: Shutdown; 2: None.
When external temperature value is
higher than it, high temp shutdown will
be issued. This value only begins to
judge after safety delay is over.
Confirm time for high temperature
shutdown detection.
When external temperature value is
higher than it, high temp warning will be
issued. This value only begins to judge
after safety delay is over.
Return value: when external temperature
value is less than or equal to it, warning
will be removed.
Confirm time for high temperature
warning detection.
When external temperature value is
lower than it, low temp warning will be
issued. This value only begins to judge
after safety delay is over.