HRX-OM-W002-A
Chapter 4 Starting the Product
4.2
Starting and Stopping
HRR Series
4-4
Fig 4-4 Restart operation when an alarm occurs
*The time to run the pump can be set within the range of "0 to 9999 seconds". The factory setting is "0
seconds". Therefore, when an alarm occurs, the operation is as in operation mode [1] .the operation
of the pump stops and the product stops. However, if the user sets the pump operation time greater
than 0s, the pump only runs until the circulating fluid discharge temperature reaches a certain value.
The factory setting is set to 40
o
C (The cut off temperature can be set by the user within the range of
10
o
C to 45
o
C. See "5.3.6 Alarm Setting Menu" for details).