Chapter 5 System Operation
HRZ Series 5.3 Operation Screen
5-17
5-17
5.3.15 Alarm Setting screen 3
Figure 5-18 Alarm Setting screen 3
Table 5-15 Alarm Setting screen 3
No.
Item
Descriptions
Setting Range
Factory Default
1
LOW DI
Allows the setting of DI value to generate 24:DI
Low Level WRN”.
Alarm is raised when DI value falls below the set
value. Alarm is cancelled if the set value is 0.
0.0 to 2.0MΩ
0.0M
[Tips]
It is displayed only if the DI Control Kit (optional) is provided.
[▲] or [▼] key is used for selecting Item” and move to other Alarm Setting
screens. And pressing the [ENT] key enabling to change the set value.
 < ALARM SET > 
LOW DI     0.0MΩ
1
POWER ON