EasyManua.ls Logo

SMC Networks HRZ002-WS-F - Initial Setting Screen 2

Default Icon
196 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HRX-OM-X010
Chapter 5 System Operation
HRZ Series 5.3 Operation Screen
5-19
5-19
5.3.17 Initial Setting screen 2
Figure 5-20 Initial Setting screen 2
Table 5-17 Initial Setting screen 2
No.
Item
Descriptions
Setting Range
Factory Default
1
REM.SD.WRITE
Store the TEMP SP and FLOW SP value
with serial communication. TEMP SP and
FLOW SP will be set to stored value after
re-turn ON the main breaker.
OFF,ON
ON
2
REM.COM.ERR
Allows the selection of system condition
when serial communication error occurs
(WRN : Stop, FLT : Continued).
WRN,FLT
WRN
3
DEVICE ADRS
*1
Allows the setting of the device address
for serial communication.
1 to 32CH
1
[Tips]
[▲] or [▼] key is used for selecting Item” and move to other Initial Setting screens.
And pressing the [ENT] key enabling to select the setting.
*1 For HRZ010-W*S-F and HRZ008-L*-F,’’SLAVE ADRS’’ is displayed.
 <INITIAL SET> 
REM.SD.WRITE ON
REM.COM.ERR  WRN
DEVICE ADRS  1CH
1
2
3
POWER ON

Table of Contents

Related product manuals