HRX-OM-X010
Chapter 5 System Operation
HRZ Series 5.3 Operation Screen
5-19
5-19
5.3.17 Initial Setting screen 2
Figure 5-20 Initial Setting screen 2
Table 5-17 Initial Setting screen 2
No.
Item
Descriptions
Setting Range
Factory Default
1
REM.SD.WRITE
Store the TEMP SP and FLOW SP value
with serial communication. TEMP SP and
FLOW SP will be set to stored value after
re-turn ON the main breaker.
OFF,ON
ON
2
REM.COM.ERR
Allows the selection of system condition
when serial communication error occurs
(WRN : Stop, FLT : Continued).
WRN,FLT
WRN
3
DEVICE ADRS
*1
Allows the setting of the device address
for serial communication.
1 to 32CH
1
[Tips]
[▲] or [▼] key is used for selecting Item” and move to other Initial Setting screens.
And pressing the [ENT] key enabling to select the setting.
*1 For HRZ010-W*S-F and HRZ008-L*-F,’’SLAVE ADRS’’ is displayed.
 <INITIAL SET> 
REM.SD.WRITE ON
REM.COM.ERR  WRN
DEVICE ADRS  1CH
1
2
3
POWER ON

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRZ002-WS-F and is the answer not in the manual?

SMC Networks HRZ002-WS-F Specifications

General IconGeneral
BrandSMC Networks
ModelHRZ002-WS-F
CategoryChiller
LanguageEnglish

Related product manuals