Chapter 6 Error Message and Troubleshooting
6.2 Troubleshooting HRZ Series
6.2 Troubleshooting
The procedure for error recovery varies with alarm types.
Alarm Code.01 to 21,24,25,28,29,32:
Eliminate the error cause. Press the [RESET] key on the operation display panel
or power cycle the main breaker to enable error recovery to take effect.
*Alarm code 28 is an alarm only for HRZ010-W*S-F.
Alarm Code.22:
Eliminate the error cause, and power cycle the main breaker to enable error
recovery to take effect.
Alarm Code.23:
Automatic error recovery is implemented upon elimination of the error.
Alarm Code.24:
This is an alarm for accessories (optional).
No alarm of this type is issued if the system is outfitted with no accessories.
Table 6-1 Troubleshooting (1/3)
The fluid is pooled at the base of
this system.
The pressure of the refirigerant
circuit exceeded the specified
value.
<Specified value>
HRZ***-WS/W1S/W2S-F:
3.0MPa
HRZ008-L/L1-F:2.5MPa
Check that facility water is being
supplied to this system.
The temperature in the
compressor was excessive.
<Specified value>
HRZ***-WS/W1S/W2S-F:
110 deg C
HRZ008-L/L1-F:110 deg C
Check that facility water is being
supplied to this system.
An insufficient amount of the
circulating fluid is observed in
the tank.
Replenish the circulating fluid.
An insufficient amount of the
circulating fluid is observed in
the tank.
Replenish the circulating fluid.
An excessive amount of the
circulating fluid is observed in
the tank.
Drain the circulating fluid.
The circulating fluid tank was
raised in temperature.
<Specified value>
Themal fuse cutout
temperature : 98 deg C
Check the load specification.
Replacement of the thermal fuse
is required.
Call the supplier for service.
The temperature of the
circulating fluid exceeded the
specified value.
<Specified value>
HRZ***-WS/W1S-F : 95 deg C
HRZ***-W2S-F : 65 deg C
HRZ008-L/L1-F : 50 deg C
Check the load specification.