Name of
the
controller
setting
software
(code)
Alarms and countermeasures
Controller
supply
voltage is
outside set
range.
(1-147)
< Details >
The power supply voltage for motor control detected by the
controller is outside of the specified range.
<Countermeasure>
Check the motor control power supply voltage connected to the
controller.
If a single power supply is used for both the control power
and the motor power, or the power supply is an “inrush
current protection type”, a voltage drop may occur during
acceleration/deceleration, which will generate an alarm.
< Details >
The alarm may be caused by regenerative power depending on
the method of operation of the actuator.
<Countermeasure>
Check if the operating condition of the actuator is within the
specification range.
Please refer to the actuator manual or the catalogue for the
method of operation of the actuator.
Current limit
is exceeded
(1-148)
< Details >
The output current accumulated value has exceeded the
specified value.
<Countermeasure>
Check if the travel of the actuator was interrupted. Also, make
sure that the load, speed, acceleration and deceleration are
within the specifications of the actuator.