-62-
No.PF※※-OMA1002
Device details status parameter (Index 37)
Event details of the readable device statuses are as follows.
Layout
Event
Event class
Event code
Definition
Value
1
Internal failure or problem
Error
0xF4
0x8D03
2
Internal failure or problem
Error
0xF4
0x8D04
3
Internal failure or problem
Error
0xF4
0x8D05
4
Internal failure or problem
Error
0xF4
0x8D01
5
Internal failure or problem
Error
0xF4
0x8D06
6
Internal failure or problem
Error
0xF4
0x8D0C
7
Internal failure or problem
Error
0xF4
0x8D0D
8
Internal failure or problem
Error
0xF4
0x8D08
9
Shielding error
Error
0xF4
0x8D09
10
Control error
Error
0xF4
0x8D0A
11
Abnormal power supply voltage
Error
0xF4
0x8D0B
12
Above the accumulated flow measurement
Warning
0xE4
0x8D80
13
Outside the output PD setting range
Warning
0xE4
0x8D90
14
Above the instantaneous flow measurement
Warning
0xE4
0x8C10
15
Below the instantaneous flow measurement
Warning
0xE4
0x8C30
16
Test event A
Warning
0xE4
0x8CA0
17
Test event B
Warning
0xE4
0x8CA1
18
Data storage upload request
Notification
0x54
0xFF91
2023-12-20 14:49
DL145266

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks PFCA7 Series and is the answer not in the manual?

SMC Networks PFCA7 Series Specifications

General IconGeneral
BrandSMC Networks
ModelPFCA7 Series
CategoryController
LanguageEnglish

Related product manuals