-73-
No.PF※※-OMA1002
Error name
Error display
Description
Measures
Control
operation in the
event of an error
Close error
(Err51)
A flow rate exceeding ±5%F.S.
is applied when the
commanded flow rate is less
than ±1%F.S.
Check the
installation so that
the direction of fluid
flow is the same as
the direction of the
arrow shown on the
side of the unit and
switch the power on
again.
Stopped
Abnormal power
supply voltage
(Err60)
The power supply voltage is
outside of the range
24 VDC±10%.
Supply a power
supply voltage
within the range
24 VDC±10%.
Stopped