-72-
No.PF※※-OMA1002
Error display
Error name
Error display
Description
Measures
Control
operation in the
event of an error
System error
(Err0, 4, 6, 8, 16, 40,
82, 83)
An internal data error has
occurred.
Turn off the power
and check for any
noise source, and
then turn on the
power again.
If the failure cannot
be solved, contact
SMC.
Stop
Over current error
(Err1)
The switch output load
current has exceeded 80 mA.
Remove the cause
of the excessive
current in the
output.
Continuing
Zero clear error
(Err3)
During a zero clear operation,
a flow rate exceeding ±5%F.S.
is applied.
Perform the
zero-clear operation
again when the flow
rate is not applied.
Continuing
Version does not
match
(Err15)
The IO-Link version does not
match with the master.
Align the master
IO-Link version to
the device.
Continuing
Control error
(Err50)
The controlled flow rate does
not continuously reach the
commanded flow rate for at
least 5 seconds.
Use the product
within the operating
differential pressure
and operating
pressure range.
Check to see if
there is any air
leakage from piping,
etc.
The controlled flow
rate is restored by
setting the
commanded flow
rate to zero.
When [Local] is
selected in control
selection setting
mode, the
controlled flow rate
is restored by
pressing and
holding the UP and
DOWN button for
1 second or longer.
Stopped
: When [Local] is
selected
2023-12-20 14:49
DL145266

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks PFCA7 Series and is the answer not in the manual?

SMC Networks PFCA7 Series Specifications

General IconGeneral
BrandSMC Networks
ModelPFCA7 Series
CategoryController
LanguageEnglish

Related product manuals