HYD 5/6/8/10/15/20KTL-3PH USER MANUAL
“System Settings” menu
In this menu you can do the basic settings which are needed to
operate the device.
Sets the display language
Sets the system time of the inverter
Sets the country and grid code
Select between Self-use mode
(Standard), time-of-use mode, timing
mode, passive mode. See “Storage
Modes” chapter for details.
With the Input Channel Configuration
you define if PV and / or batteries are
connected and in what configuration.
If a battery is connected to BAT1
input, select “Bat Input1”, otherwise
“Not Use”
if a second battery is connected to
BAT2 independently, select “Bat
Input2”
If one battery is connected in parallel
to BAT1 and BAT2, select “Bat Input1”,
otherwise “Not Use”
if PV strings are connected to PV1
independently, select “PV Input 1”,
otherwise “Not Use”
if PV strings are connected to PV2
independently, select “PV Input 2”
If PV strings are connected to PV2 in
parallel to PV1, select “PV Input 1”,
otherwise “Not Use”
Enable / Disable the emergency
power supply mode (EPS). It is only
available if a battery is connected
Enter the Modbus address (when
several inverters require simultaneous
monitoring), standard: 01
Baud Rate: The default baud rate is
9600