90 • Starting Procedure
_____________________________________________________________________________________________
8.1 Standard Starting Procedure
See next page
Connect Control Supply voltage. On LED will light.
Review all parameters with the Mode and Select keys. Set parameters as required.
If necessary, return to default parameters (refer to section
7.5.3 page 63).
Connect mains voltage to the line terminals of the RVS-DN.
Set LCD to show % OF MOTOR FLA.
Apply START command
Motor starts to turn
shortl
y
after START
Initial inrush current or
mechanical shock is
too high?
Increase INITIAL VOLTAGE and start again
Decrease INITIAL VOLTAGE and start again
Speed accelerates
smoothly to nominal?
A
pp
l
y
the STOP command and wait until the motor sto
p
s.
Sli
g
htl
y
increase INITIAL VOLTAGE
Current during
acceleration is too
high?
Decrease CURRENT LIMIT
Motor speed does not
accelerate to nominal?
Increase CURRENT LIMIT
Yes
No
Yes
No
No
Yes Yes
No
No
Yes
A