PID-6251-SETTINGS v1
Table 502: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
FineSyncSource Off
GPS
IRIG-B
GPS+IRIG-B
-
- Off Fine time synchronization source
SyncMaster Off
SNTP-Server
- - Off Activate IEDas synchronization master
AppSynch NoSynch
Synch
- - NoSynch Time synchronization mode for
application
SyncAccLevel Class T5 (1us)
Class T4 (4us)
Unspecified
-
- Unspecified Wanted time synchronization accuracy
PID-6638-SETTINGS v3
Table 503: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
CoarseSyncSrc Off
SPA
LON
DNP
IEC103
-
- Off Coarse time synchronization source
FineSyncSource Off
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
- - Off Fine time synchronization source
SyncMaster Off
SNTP-Server
- - Off Activate IEDas synchronization master
TimeAdjustRate Slow
Fast
- - Fast Adjust rate for time synchronization
HWSyncSrc Off
GPS
IRIG-B
PPS
-
- Off Hardware time synchronization source
SyncLostMode NoBlock
Block
BlockOnLostUTC
-
- NoBlock Behavior of dependent protection
functions when time synchronization
quality is inadequate
SyncAccLevel
Class T5 (1us)
Class T4 (4us)
Unspecified
-
- Unspecified Wanted time synchronization accuracy
CurrentSyncSource 0 - 16 - 1 - Current synchronization source
PTPGMId 0 - 16 - 1 - PTP Grand Master Id
PTPGMClass 0 - 16 - 1 - PTP Grand Master Class
Table continues on next page
Section 16 1MRK 505 384-UEN A
Basic IED functions
646 Breaker protection REQ650 2.2 IEC