Chapter 5 Removing and Replacing Miscellaneous Internal Components 87
Installing the Hardware Cryptographic Module
1. Press the retaining standoff into the system board.
2. Insert the hardware cryptographic module onto the retaining standoff and
connector on the system board (
FIGURE 5-10).
3. Press the hardware cryptographic module down to fully seat it.
4. Insert all PCI cards back into the PCI riser card assembly.
See “Installing a PCI Card” on page 80.
5. Install the air duct and rear fan assembly.
See “Installing or Closing the Air Duct and Rear Fan Assembly” on page 70.
6. Close the rotating service module.
See “Closing the Rotating Service Module” on page 31.
7. Install the server cover.
See “Installing the Server Cover” on page 29.
8. Power on the server.
See “Powering On the Server” on page 20.
For information on configuring and using the hardware cryptographic module, refer
to the documentation that is shipped with it.
System Board Assembly
Caution – The assembly might be very hot. Let it cool before beginning this
procedure.
Removing the System Board
1. Power off the server.
See “Powering Off the Server” on page 22.
2. Remove the server cover.
See “Removing the Server Cover” on page 27.