EasyManuals Logo

Sunfar C300 Series User Manual

Default Icon
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
20 SUNFAR C300
C300 series of non-sensor current vector-control inverter manual
Parameters’
Types
Function Code Name Setting range
Minimum
Setting
Manufacture
Setting
Modify
Limit
F0.5
Combination methods
of running the command of
terminals
0Two-line mode 1
1Two-line mode 2
2Three-line mode
1 0
F0.6 Steering control
The first part of LED (form right to left):
0Running direction is consistent with
setting
direction
1Running direction is opposite to setting
direction
The second part of LED
0Prevention REV is valid
1Prevention REV is invalid
The third and fourth part of LED(form
right to left)Reserved
1 0000
F0.7 The lower limit frequency 0.0 Hz~ [F0.8] 0.01 0.0
F0.8 The upper limit frequency [F0.7] ~ 400.00Hz 0.01 50.00
F0.9 Reserved
F0.10 Acc time 1 0.1 ~ 6000 Sec/Min 0.1
F0. 11 Dec time 1 0.1 ~ 6000 Sec/Min 0.1
Basic operation parameter unit
F0. 12
Characteristics parameters
of Acc and Dec
The first part of LED (form right to left):
0Beeline 1Scurve
The second part of LED
0Output freq. will be modified according
to Acc/Dec time.
1Output freq. will be automatically
modified according to lode.
The third part ofLEDUnit of Acc/Dec
time
0Sec 1Min
The third and fourth part of LED:
Reserved
1 0000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sunfar C300 Series and is the answer not in the manual?

Sunfar C300 Series Specifications

General IconGeneral
BrandSunfar
ModelC300 Series
CategoryInverter
LanguageEnglish

Related product manuals