SUNFAR C300 67
C300 series of non-sensor current vector-control inverter manual
[F5.1]~[F5.8] Multi-speed freq.1~8
Those parameters are used for setting output freq. of multi-speed.
[F5.9]~[F5.16] Running time of Multi-speed 1~8
Those parameters are used for confirming running time of each stage.
[F5.17]~[F5.18] Running direction of PLC multi-speed
Those parameters are used for defining running direction of PLC multi-speed.
[F5. 17]
The first part of LED(form right to left):
0: Stage 1 FWD 1:Stage 1 REV
The second part of LED:
0: Stage 2 FWD 1:Stages 2 REV
The third part of LED:
0: Stage 3 FWD 1:Stages 3 REV
The fourth part of LED:
0: Stage 4 FWD 1:Stages 4 REV
[F5. 18] :
The first part of LED(form right to left):
0: Stage 5 FWD 1:Stages 5 REV
The second part of LED:
0: Stage 6 FWD 1:Stages 6 REV
The third part of LED:
0: Stage 7 FWD 1:Stages 7 REV
The fourth part of LED:
0: Stage 8 FWD 1:Stages 8 REV
6.7
Advanced running parameter unit
F6.1 is used for resetting some faults and run again.
F6.2 defines interval time between fault starting and fault recovery. If inverter can’t
recover in setting value of F6.1, it will output fault signal. Inverter will check speed
and restart.
F6.0 Reserved
F6.1 Fault self-recovery time Setting range:0 ~ 2
F6.2 Interval time of fault self-recovery Setting range:0.2 ~ 20.0s
F5.19 Reserved
Inverter can’t self-recovery about overheat or overload protect.