EasyManua.ls Logo

Sunfar C300 Series - Advanced Running Parameters: Fault Recovery

Default Icon
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SUNFAR C300 67
C300 series of non-sensor current vector-control inverter manual
[F5.1][F5.8] Multi-speed freq.18
Those parameters are used for setting output freq. of multi-speed.
[F5.9][F5.16] Running time of Multi-speed 1~8
Those parameters are used for confirming running time of each stage.
[F5.17][F5.18] Running direction of PLC multi-speed
Those parameters are used for defining running direction of PLC multi-speed.
[F5. 17]
The first part of LED(form right to left)
0 Stage 1 FWD 1Stage 1 REV
The second part of LED
0 Stage 2 FWD 1Stages 2 REV
The third part of LED
0 Stage 3 FWD 1Stages 3 REV
The fourth part of LED
0 Stage 4 FWD 1Stages 4 REV
[F5. 18]
The first part of LED(form right to left)
0 Stage 5 FWD 1Stages 5 REV
The second part of LED
0 Stage 6 FWD 1Stages 6 REV
The third part of LED
0 Stage 7 FWD 1Stages 7 REV
The fourth part of LED
0 Stage 8 FWD 1Stages 8 REV
6.7
Advanced running parameter unit
F6.1 is used for resetting some faults and run again.
F6.2 defines interval time between fault starting and fault recovery. If inverter can’t
recover in setting value of F6.1, it will output fault signal. Inverter will check speed
and restart.
F6.0 Reserved
F6.1 Fault self-recovery time Setting range0 ~ 2
F6.2 Interval time of fault self-recovery Setting range0.2 ~ 20.0s
F5.19 Reserved
Inverter can’t self-recovery about overheat or overload protect.

Table of Contents

Related product manuals