2. INSTALLATION GUIDELINES
2.1 Environmental Requirements
If users demand any special requirements of installation, please contact us firstly.
C300 series of inverter is in hanging model, so it should be installed in vertical way.
In order to ensure the air circulation around the inverter to be cool, there should be
enough space around the inverter (Fig. 2-1-A). Add the air deflector when apply the
up-down installation (Fig. 2-1-B).
Inverter
Inverter
Air flow
clapboard
Fig2-1-B Multi-inverter Installation
Fig2-1-A Interval distance
Above 120mm
Above 5mm
Above 120mm
Above 50mm
Fan ventilation
1. Be sure to install the inverte
in a well-ventilated room.
2. Ambient temperature is from -10℃ to 40℃.
3. Please avoid putting the inverter in a high temperature and moist
location. The humidity is less than 90% and non-condensing.
4. Keep away from combustible, explosive materials and caustic gas or
liquid.
5. No dust, floating fiber and metal particles.
6. The inverter must be installed in a firm and no vibration location.
7. The installation plane should be solid and not vibrant.