36 SUNFAR C300
C300 series of non-sensor current vector-control inverter manual
Parameters’
Types
Function Code Name Setting range
Minimum
Setting
Manufacture
Setting
Modify
Limit
F9.1 Local address 0~30 1 0
F9.2 Response delay of local 0~1000ms 1 5ms
F9.3
Function setting of
communication
auxiliary function
The first part of LED(form right to left):
0: The inverter is guest
1: The inverter is host
The second part of LED:
Act selection after communication is lost
0:Stop 1:Keep
The third part of LED: Reserved.
The fourth part of LED:
Communication protocol setting, from 0
to 2
1 0000
F9.4
Checkout time of
communication overtime
0.0~100.0s 0.1 10.0
F9.5 Linkage setting proportion 0.01~10.00 0.01 1.00
F9.6
Rectify channel of
linkage setting proportion
0:Close 1:Panel potentiometer
2:External voltage signal VC(0 ~ 10V)
3:External current signal CC(0 ~ 20mA)
1 0
Serials communication parameters
F9.7 Reserved
FC.0
Under voltage protection
level
360~460V 1 380
FC.1 Over voltage limit level 660~760V 1 700
FC.2
Current amplitude limiting
level
150~200(%) 1 180
Special function
parameter unit
FC.3 Reserved