105
Fault name
Triggering
condition
Recovery
condition
Corrective measures
Drive Board
Fault
IGBT feedback
node signal is
abnormal (drive
power undervoltage,
module conduction
through, etc.).
IGBT
feedback
node signal
returns to
normal.
Reboot the machine. If the fault
persists, please contact SUNGROW.
Neutral
Point Shift
The Bus voltage
difference between
the positive and
negative ends
exceeds 260 V or
half-Bus voltage
exceeds 800V for
920 us.
The fault is
cleared once
the voltage
returns to
normal for
1s
Reboot the machine. If the fault
persists, please contact SUNGROW.
Carrier
Sync Flt
The carrier
synchronization line
between parallel
units is abnormal,
causing the slave
unit can not run
synchronously with
the master unit for
10 ms, and the
slave unit is in non-
operating status for
10 s. The fault
signal is uploaded
by CPLD.
The fault is
cleared once
the carrier
returns to
normal for
10 s.
1. Try to power down and reboot the
machine;
2. Check the carrier synchronization
line to make sure that there are no
loose connections;
3. If the fault is not caused by the
foregoing reasons and still exists,
please contact SUNGROW.
System Manual 11 Troubleshooting

Table of Contents

Other manuals for Sungrow SC3150UD-MV-US

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SC3150UD-MV-US and is the answer not in the manual?

Sungrow SC3150UD-MV-US Specifications

General IconGeneral
BrandSungrow
ModelSC3150UD-MV-US
CategoryStorage
LanguageEnglish

Related product manuals