91
8
System Decommissioning
8.1 Disconnecting Inverter
Danger of burns!
Even if the inverter is shut down, it may still be hot and cause burns. Wear protec-
tive gloves before operating the inverter after it cools down.
For maintenance or other service work, the inverter must be switched off.
Proceed as follows to disconnect the inverter from the AC and DC power sources. Lethal
voltages or damage to the inverter will follow if otherwise.
Step 1 Disconnect the external AC circuit breaker and prevent it from inadvertent reconnection.
Step 2 Rotate the DC switch(if there is) to the "OFF" position for disconnecting all of the PV string
inputs.
Step 3 Wait about 5 minutes until the capacitors inside the inverter completely discharge.
Step 4 Ensure that the DC cable is current-free with a current clamp.
- - End
8.2 Dismantling the Inverter
Risk of burn injuries and electric shock!
After the inverter is powered off for 5 minutes, measure the voltage and current
with professional instrument. Only when there is no voltage nor current can opera-
tors who wear protective equipment operate and maintain the inverter.
Before dismantling the inverter, disconnect the inverter from both AC and DC
power sources.
If there are more than two layers of inverter DC terminals, dismantle the outer
DC connectors before dismantling the inner ones.
If the original packing materials are available, put the inverter inside them and
then seal them using adhesive tape. If the original packing materials are not
available, put the inverter inside a cardboard box suitable for the weight and
size of this inverter and seal it properly.

Table of Contents

Other manuals for Sungrow SG50CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX and is the answer not in the manual?

Sungrow SG50CX Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated AC Output Power50 kW
Max. AC Output Current76 A
Frequency50 Hz / 60 Hz
Efficiency98.6%
Start Voltage200 V
Number of DC Inputs per MPPT2
Max. AC Apparent Power55 kVA
AC Voltage Range310 V - 480 V
Power Factor at Rated Power1
Adjustable Power Factor Range0.8 leading - 0.8 lagging
THDi< 3%
DC SwitchYes
AC Surge ProtectionType II
DC Surge ProtectionType II
Protection ClassI
Cooling MethodSmart forced air cooling
Protection DegreeIP66
Protection LevelIP66
Operating Temperature Range-25°C to +60°C
Humidity0-100%
AC Output Voltage3 / N / PE, 220 V / 380 V, 230 V / 400 V

Related product manuals