104
Touching the PCB or other static sensitive components may cause damage to the
device.
Do not touch the circuit board unnecessarily.
Observe the regulations to protect against electrostatic and wear an anti-static
wrist strap.
If the earth fault occurs, the DO dry-contact will switch on automatically to signal
the external alarm. The LED will turn red and a beeping sound will alarm until the
fault is rectified, for internet connected products the error will also be sent to the
portal.
9.2.2 Routine Maintenance
Item Method Period
Device clean
Check whether the air outlet and heat
sink are blocked by dust and other
objects.
Check if the air inlet and outlet are
normal. Clean the air inlet and outlet,
if necessary.
Six months to a year
(depend on the dust con-
tents in air)
Fans
Check whether there is a fan alarm on
the App.
Check whether there is any abnormal
noise when the fan is rotating.
Clean or replace the fans if necessary
(see the following section).
Once a year
Cable entry
Check whether the cable entry is in-
sufficiently sealed or the gap is exces-
sively large, and reseal the entry
when necessary.
Once a year
Electrical
connection
Check whether cables are loose or fall
off.
Check whether the cable is damaged,
especially the part in contact with the
metal enclosure.
Six months to a year
9 Troubleshooting and Maintenance User Manual

Table of Contents

Other manuals for Sungrow SG50CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX and is the answer not in the manual?

Sungrow SG50CX Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated AC Output Power50 kW
Max. AC Output Current76 A
Frequency50 Hz / 60 Hz
Efficiency98.6%
Start Voltage200 V
Number of DC Inputs per MPPT2
Max. AC Apparent Power55 kVA
AC Voltage Range310 V - 480 V
Power Factor at Rated Power1
Adjustable Power Factor Range0.8 leading - 0.8 lagging
THDi< 3%
DC SwitchYes
AC Surge ProtectionType II
DC Surge ProtectionType II
Protection ClassI
Cooling MethodSmart forced air cooling
Protection DegreeIP66
Protection LevelIP66
Operating Temperature Range-25°C to +60°C
Humidity0-100%
AC Output Voltage3 / N / PE, 220 V / 380 V, 230 V / 400 V

Related product manuals