102
Fault
Code
Fault
Name
Possible
Cause
Corrective Method
32
Overtem-
perature
The oper-
ating tem-
perature is
too high
1. Take measures to reduce the temperature,
such as improving heat dissipation conditions.
2. Check whether the alarm still exists in the early
morning or evening.
3. If the alarm still exists with correct settings,
please contact Sungrow Customer Service.
128
Output
current
backfeed
The output
current of
the opti-
mizer
backfeeds
1. If strings are connected in parallel, check
whether the number of modules varies consider-
ably between the two strings, or the module is se-
verely shaded.
2. If the alarm persists, please contact Sungrow
Customer Service.
512
Hardware
fault
A hardware
fault occurs
to the
optimizer
Please contact Sungrow Customer Service.
1024
Update
failed
The opti-
mizer soft-
ware fails
to upgrade
1. Check the light condition, and update the opti-
mizer again if the light is normal.
2. If the fault persists, please contact Sungrow
Customer Service.
If there is a string current backfeed fault, first check whether the optimizer is
offline.
Contact the dealer if the measures listed in the “Troubleshooting Method” col-
umn have been taken but the problem persists. Contact SUNGROW if the
dealer fails to solve the problem.
9 Troubleshooting and Maintenance User Manual

Table of Contents

Other manuals for Sungrow SG50CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX and is the answer not in the manual?

Sungrow SG50CX Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated AC Output Power50 kW
Max. AC Output Current76 A
Frequency50 Hz / 60 Hz
Efficiency98.6%
Start Voltage200 V
Number of DC Inputs per MPPT2
Max. AC Apparent Power55 kVA
AC Voltage Range310 V - 480 V
Power Factor at Rated Power1
Adjustable Power Factor Range0.8 leading - 0.8 lagging
THDi< 3%
DC SwitchYes
AC Surge ProtectionType II
DC Surge ProtectionType II
Protection ClassI
Cooling MethodSmart forced air cooling
Protection DegreeIP66
Protection LevelIP66
Operating Temperature Range-25°C to +60°C
Humidity0-100%
AC Output Voltage3 / N / PE, 220 V / 380 V, 230 V / 400 V

Related product manuals