EasyManuals Logo

Sungrow SG50CX User Manual

Sungrow SG50CX
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
4
Danger to life due to a high voltage inside the inverter!
Be sure to use special insulation tools during cable connections.
Note and observe the warning labels on the product, and perform operations
strictly following the safety instructions.
Respect all safety instructions listed in this manual and other pertinent
documents.
Damage to the product caused by incorrect wiring is not covered by the warranty.
Electrical connection must be performed by professionals.
All cables used in the PV generation system must be firmly attached, properly
insulated, and adequately dimensioned.
Check the positive and negative polarity of the PV strings, and connect the PV
connectors to corresponding terminals only after ensuring polarity correctness.
During the installation and operation of the inverter, please ensure that the posi-
tive or negative poles of PV strings do not short-circuit to the ground. Other-
wise, an AC or DC short-circuit may occur, resulting in equipment damage. The
damage caused by this is not covered by the warranty.
Do not connect any load between the inverter and the AC circuit breaker di-
rectly connected to it, so as to prevent the switch from tripping by mistake.
Determine the specifications of AC switch strictly in compliance with the appli-
cable local laws and regulations and safety standards or the recommendation
by SUNGROW. Otherwise, the switch may not open in time in the event of some-
thing abnormal, which may then lead to safety incidents.
Comply with the safety instructions related to PV strings and the regulations re-
lated to the local grid.
1 Safety Instructions User Manual

Table of Contents

Other manuals for Sungrow SG50CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX and is the answer not in the manual?

Sungrow SG50CX Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated AC Output Power50 kW
Max. AC Output Current76 A
Frequency50 Hz / 60 Hz
Efficiency98.6%
Start Voltage200 V
Number of DC Inputs per MPPT2
Max. AC Apparent Power55 kVA
AC Voltage Range310 V - 480 V
Power Factor at Rated Power1
Adjustable Power Factor Range0.8 leading - 0.8 lagging
THDi< 3%
DC SwitchYes
AC Surge ProtectionType II
DC Surge ProtectionType II
Protection ClassI
Cooling MethodSmart forced air cooling
Protection DegreeIP66
Protection LevelIP66
Operating Temperature Range-25°C to +60°C
Humidity0-100%
AC Output Voltage3 / N / PE, 220 V / 380 V, 230 V / 400 V