3.6 Alarm Sign
3.6.1 Alarm Message
3.6.2 Prompt Message
Message Alarm Cause Solution
Gross Weight Upper
Limit
Gross Weight Upper Limit.
Refer to parameter [204]-[207] Gross Weight
Upper Limit’.
Deviation Alarm
Positive Deviation Alarm.
Negative Deviation Alarm.
Refer to parameter [200] ‘Allowed Positive
Deviation’ and [201] ‘Allowed Negative
Deviation’.
Pause Alarm
For Deviation Alarm.
Refer to parameter [310]
Auto Pause for
Deviation Alarm’.
It’s allowed to do ‘Manual SP3 Re-feed’ for
Negative Deviation Alarm.
Press DI button ‘Start / Clear Alarm’ to recover
running.
For Gross Weight Upper Limit
Alarm.
After fault handling, press DI button ‘Start / Clear
Alarm’ to recover running.
For Feeding Overtime Alarm.
Feeding Overtime Feeding TimeT6.
Refer to parameter [406] T6
Max. Feeding
Time’.
Dumping Overtime Dumping TimeT7.
Refer to parameter [407] ‘T7 Max. Dumping
Time’.
Message Alarm Cause Solution
Target Batch
Finished
Alarm or Auto-stop with ‘Target
Batch Finished’.
Refer to parameter [203] ‘Target Batch and [301]
Target Batch Control’.
Last Batch
It’s in the batch
ing process of the
last batch.
The message will disappear after the present batch
finished.
ZERO Invalid Over ‘Zero Fine Adjusting Range’.
Refer to parameter [123]
‘Zero Fine Adjusting
Range’.