33
6.3.4 Working Mode Parameters
No. Sign Range Default Description REG
300
Application
Mode
0~4
1
[*]
Application Mode
0: APP1 Single-scale Mode
1: APP2 Four-scale Mode
Authorization: Administrator.
40301
301
Target Batch
Control
0~1 0
Target Batch Control
0: OFF
1: ON [With Target Batch finished, the
batching process will stop automatically]
40303
302
Auto Zero Cycle
Interval
0~99 10
Auto Zero Cycle Interval
Set value=0: No doing
Auto Zero Fine
Adjustment’.
Set value > 0: To the first two batches after Start
signal inputted, the controller will do Auto Zero
Fine Adjustment [without power-down protection]
before feeding; then to the next batch, only after
Batch Count reached to this set value, the controller
will do Auto Zero Fine Adjustment before
feeding.
40305
303 Unused 0 0 Unused 40307
304
DO Feedings
Start Mode
0~1 0
DO Feedings Start Mode
0: Together [SP1&SP3]
1: In Order [SP1-SP3]
40309
305
SP3 Low-speed
Feeding Mode
0~1 0
SP3 Low-speed Feeding Mode
0: Continuous [Continuous Feeding Mode]
1: Inching [Inching Feeding Mode: SP3 works with
Inching Feeding Mode in Low-speed Feeding
process. Inching DO outputs ON/OFF; Inching AO
outputs 0V/‘Control Voltage for SP3 Low-speed
Feeding’]
40311
306
t1 SP3 ON
Holding Time
0.03
~9.99
0.50
t1SP3 ON Holding Time [s]
Used for SP3 Inching Feeding Mode.
40313
307
t2 SP3 OFF
Holding Time
0.03
~9.99
0.50
t2SP3 OFF Holding Time [s]
Used for SP3 Inching Feeding Mode.
40315
[*]: Part-Default operation has no effect on the parameter.