TMSL 097-45018-02 Issue 3: Mar 96
Page 60
REPORT EVENT (Contd)
conddescr: DISCIPLINING REFERENCE = working facility switched back to
SWITCHED working status
LOSS OF STRATUM A INPUT = input from clock in ST A slot has been
lost
LOSS OF STRATUM B INPUT = input from clock in ST B slot has been
lost
THRESHOLD VIOLATION = BPV errors exceed the BPV threshold
FOR BPV
THRESHOLD VIOLATION = OOF errors exceed the OOF threshold
FOR OOF
THRESHOLD VIOLATION = AIS errors exceed the AIS threshold
FOR CRC
ALARM INDICATION = an alarm indication signal has been
SIGNAL RECEIVED received
ST SYNTH SIGNAL FREQ = the synthesized signal from the clock
VIOLATION card is showing frequency drift
THRESHOLD VIOLATION = an MTIE threshold has been exceeded
FOR MTIE OBSERVATION
THRESHOLD VIOLATION = threshold for MTIE 1-second
FOR MTIE1 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = threshold for MTIE 4-second
FOR MTIE4 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = threshold for MTIE 16-second
FOR MTIE16 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = threshold for MTIE 64-second
FOR MTIE64 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = threshold for MTIE 128-second
FOR MTIE128 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = threshold for MTIE 512-second
FOR MTIE512 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = threshold for MTIE 900-second
FOR MTIE900 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 1-second
FOR TVAR1 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 4-second
FOR TVAR4 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 16-second
FOR TVAR16 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 64-second
FOR TVAR64 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 128-second
FOR TVAR128 OBSERVATION observation has been exceeded

Table of Contents

Other manuals for Symmetricom TimeProvider 500 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 500 series and is the answer not in the manual?

Symmetricom TimeProvider 500 series Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 500 series
CategoryData Loggers
LanguageEnglish

Related product manuals