Issue 3: Mar 96 TMSL 097-45018-02
Page 55
REPORT ALARM
(REPT-ALM{EQPT|T1})
MESSAGE CATEGORY: SURVEILLANCE
TYPE: AUTOMATIC
This message reports the occurrence of alarmed events, including the access identifier, the severity of
the alarm, the type of condition, whether it affects service, and a short description of the alarm.
MESSAGE FORMAT
<sid> <date> <time>
<almcde> <atag> REPT ALM {EQPT|T1}
"<aid>:<ntfcncde>,<condtype>,<srveff>:<conddescr>"
;
almcde: *C = critical alarm
** = major alarm
* = minor alarm
A = automatic message (only if a following ntfcncde is CL or NA)
aid: ALL = all DCD-500 object entities
CLK-1 = Stratum clock unit A
CLK-2 = Stratum clock unit B
EXPANS = expansion shelf
FUSE-1 = fuse A
FUSE-2 = fuse B
MASTER = master shelf
MRC-1-x = Multi-Reference Controller A (x = span 1 to 4)
MRC-2-x = Multi-Reference Controller B (x = span 1 to 4)
PSM-x-y = Precision Sync Monitor card (x = 1 to 9, y = span 1 to 4)
MIS = Maintenance Interface, System
GTI-1 = GTI installed in the A slot
GTI-2 = GTI installed in the B slot
SYSTEM = all clocks have failed
ntfcncde: CR = critical alarm
MJ = major alarm
MN = minor alarm
CL = cleared alarm
NA = not alarmed

Table of Contents

Other manuals for Symmetricom TimeProvider 500 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 500 series and is the answer not in the manual?

Symmetricom TimeProvider 500 series Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 500 series
CategoryData Loggers
LanguageEnglish

Related product manuals