Issue 3: Mar 96 TMSL 097-45018-02
Page 55
REPORT ALARM
(REPT-ALM{EQPT|T1})
MESSAGE CATEGORY: SURVEILLANCE
TYPE: AUTOMATIC
This message reports the occurrence of alarmed events, including the access identifier, the severity of
the alarm, the type of condition, whether it affects service, and a short description of the alarm.
MESSAGE FORMAT
<sid> <date> <time>
<almcde> <atag> REPT ALM {EQPT|T1}
"<aid>:<ntfcncde>,<condtype>,<srveff>:<conddescr>"
;
almcde: *C = critical alarm
** = major alarm
* = minor alarm
A = automatic message (only if a following ntfcncde is CL or NA)
aid: ALL = all DCD-500 object entities
CLK-1 = Stratum clock unit A
CLK-2 = Stratum clock unit B
EXPANS = expansion shelf
FUSE-1 = fuse A
FUSE-2 = fuse B
MASTER = master shelf
MRC-1-x = Multi-Reference Controller A (x = span 1 to 4)
MRC-2-x = Multi-Reference Controller B (x = span 1 to 4)
PSM-x-y = Precision Sync Monitor card (x = 1 to 9, y = span 1 to 4)
MIS = Maintenance Interface, System
GTI-1 = GTI installed in the A slot
GTI-2 = GTI installed in the B slot
SYSTEM = all clocks have failed
ntfcncde: CR = critical alarm
MJ = major alarm
MN = minor alarm
CL = cleared alarm
NA = not alarmed