Issue 3: Mar 96 TMSL 097-45018-02
Page 59
REPORT EVENT
(REPT-EVT)
MESSAGE CATEGORY: SURVEILLANCE
TYPE: AUTOMATIC
This message reports the occurrence of nonalarmed events, including the access identifier, the severity
of the alarm, the type of condition, whether it affects service, and a short description of the alarm.
MESSAGE FORMAT
<sid> <date> <time>
<atag> REPT EVT {EQPT|T1}
"<aid>:<condtype>,<condeff>:<conddescr>"
;
aid: MRC-1-x = Multi-Reference Controller A (x = span 1 to 4)
MRC-2-x = Multi-Reference Controller B (x = span 1 to 4)
PSM-x-y = Precision Sync Monitor card (x = 1 to 9, y = span 1 to 4
or ALL)
CLK-1 = clock card A
CLK-2 = clock card B
condtype: AIS = alarm indication signal
FFREQ = fractional frequency exceeded for ST A or ST B
LOS = loss of signal
SFI = loss of stratum input
TBPV = threshold violation for BPVs
TCRC = threshold violation for CRC errors
TFFREQ = threshold for fractional frequency has been exceeded
TMTIE = an MTIE threshold has been exceeded
TMTIE1 = threshold for MTIE 1 second has been exceeded
TMTIE4 = threshold for MTIE 4 seconds has been exceeded
TMTIE16 = threshold for MTIE 16 seconds has been exceeded
TMTIE64 = threshold for MTIE 64 seconds has been exceeded
TMTIE128 = threshold for MTIE 128 seconds has been exceeded
TMTIE512 = threshold for MTIE 512 seconds has been exceeded
TMTIE900 = threshold for MTIE 900 seconds has been exceeded
TOOF = threshold for OOFs has been exceeded
TTVAR1 = time variance for TVAR 1 second has been exceeded
TTVAR4 = time variance for TVAR 4 seconds has been exceeded
TTVAR16 = time variance for TVAR 16 seconds has been exceeded
TTVAR64 = time variance for TVAR 64 seconds has been exceeded
TTVAR128 = time variance for TVAR 128 seconds has been exceeded
WKSWPRx = working facility switched back to working status
(x = equipment number)
condeff: CL = standing condition cleared
SC = standing condition raised

Table of Contents

Other manuals for Symmetricom TimeProvider 500 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 500 series and is the answer not in the manual?

Symmetricom TimeProvider 500 series Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 500 series
CategoryData Loggers
LanguageEnglish

Related product manuals