TMSL 097-45018-02 Issue 3: Mar 96
Page 58
REPORT ALARM (Contd)
conddescr (Contd):
THRESHOLD VIOLATION = time variance for TVAR 1-second
FOR TVAR1 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 4-second
FOR TVAR4 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 16-second
FOR TVAR16 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 64-second
FOR TVAR64 OBSERVATION observation has been exceeded
THRESHOLD VIOLATION = time variance for TVAR 128-second
FOR TVAR128 OBSERVATION observation has been exceeded
<null> = no descriptive information exists
For GTI only:
FUSE OR POWER FAIL = DCD-LPR fuse has blown, or the office
battery has failed
GPS LOSS OF SIGNAL = GPS loss of signal
GPS INVALID = GPS timing is invalid
GTI OUT FAULT = primary rate output of the GTI has been
faulted by a short, improper termination,
or equipment failure
GTI-FAIL = hardware failure; for field service/engi-
neering use only
OSCA LOSS OF SIGNAL = no signal energy detected on OSC input
GTR POWER FAULT = power supply has been faulted by a short,
an open, or equipment failure
GTR COMM FAILURE = The GTI has timed out waiting for a sta-
tus message from the GTR
GTR FAIL = hardware failure; for field service/engi-
neering use only
Example:
TELECOMSOLUTIONS 95-12-08 15:41:32
* 14 REPT ALM EQPT
"CLK-1:MN,HLDOVRSYNC,NSA:\"CLOCK IN HOLDOVER\""
;
This example, tagged as automatic message 14, shows that clock 1 has a minor alarm, the clock is
in holdover, and service is not affected.
REFERENCE
TA-TSY-000309, Issue 1, December 1990