2.4 V/F CONTROL
2.4.1 AUTOMATIC SETTING OF WORKING VOLTAGE/FREQUENCY
“V/f control” manages the an asynchronous motor without feedback.
This type of control has a good dynamic performance also in flux weakening area (4-5 times base
frequency) and it’s able to start the motor also with high load (2 times the nominal motor torque), but
Name Description Min Max Default UM Scale
EN_VF_CNTL C80 - Enable V/f control 0 1 0 1
PRC_VF_SLIP_CMP
P170 - Slip motor
compensation
0.0 400.0 0.0
%
PRC_MOT_F_MAX
40.96
VF_TF_SLIP_CMP
P171 - Slip compensation
factor filter
0.0 150.0 35.0 ms 10
PRC_VF_BOOST
P172 - Stator voltage drop
compensation
0.0 400.0 70.0
%
PRC_DELTA_VRS
40.96
VF_EN_DCJ C83 - Enable dc brake 0 1 0 1
PRC_VF_DCJ_I_MAX
P173 - Current limit during
continuous braking
0.0 100.0 100.0 % DRV_I_NOM 40.96
PRC_VF_DCJ_F_MAX
P174 - Continuous breaking
maximum frequency limit
0.0 100.0 0.0
%
PRC_MOT_F_MAX
40.96
VF_EN_CHR_AUTOSET
C88 - Calculate V/f
characteristic nominal knee
0 1 0 1
PRC_VF_CHR_V1
P175 - V/f characteristic
point 1 voltage
0.0 100.0 0.0
%
PRC_MOT_V_MAX
40.96
PRC_VF_CHR_F1
P176 - V/f characteristic
point 1 frequency
0.0 100.0 0.0
%
PRC_MOT_F_MAX
40.96
PRC_VF_CHR_V2
P177 - V/f characteristic
point 2 voltage
0.0 100.0 0.0
%
PRC_MOT_V_MAX
40.96
PRC_VF_CHR_F2
P178 - V/f characteristic
poitn 2 frequency
0.0 100.0 0.0
%
PRC_MOT_F_MAX
40.96
PRC_VF_V_REG_D
P183 - Voltage regulator
derivative coefficient
multiplying term
0.0 100.0 100.0 % 327.67
VF_EN_SEARCH
C84 - Enable search during
motor rotation
Range
0 1
0 No
1 Freq +
2 Freq -
3 Rif 0 +
4 Rif 0 -
PRC_VF_FSTART_SEARCH
P184 - Initial search
frequency with rotating
motor
0.0 100.0 100.0
%
PRC_MOT_F_MAX
40.96
PRC_VF_FMIN_SEARCH
P185 - Minimum search
frequency with rotating
motor
0.0 100.0 2.9
%
PRC_MOT_F_MAX
40.96
PRC_VF_T_MAX_SEARCH
P191 - Torque limit during
fly restart
0.0 100.0 150.0 % DRV_T_NOM 40.96
VF_EN_STALL_ALL C82 - Enable stall alarm 0 1 1 1
VF_STALL_TIME
P186 - Working time during
limit
1 100 30 s 40.96
PRC_VF_V_MAX_STATIC
P187 - Vs amplitude
maximum static value
0.0 100.0 97.5
%
PRC_MOT_V_MAX
327.67
VF_EN_ENGY C86 - Enable energy saving 0 1 0 1
VF_TI_ENGY
P188 - Energy saving
regulator filter time constant
100 2000 400 ms 1
PRC_VF_FLX_MIN_ENGY
P189 - Energy saving
admissible minimum flux
0.0 100.0 20.0 % MOT_FLX_NOM 40.96
VF_TF_I_MAX_AL P190 - Current alarm filter 0.0 150.0 10.0 ms 10
VF_EN_OPEN_LOOP
C85 - Enable open loop
working state
Range
0 1
0 No
1
Imax
in V/f
2
Imax
in V
VF_EN_BYPASS
C87 - Enable flux angle
bypass - frequency input
0 1 0 1