TDK-Lambda GH10-150 - Output Subsystem

TDK-Lambda GH10-150
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
106
4.14.6 Output Subsystem
OUTPut[:STATe] <Bool>
Function Enables / Disables the power supply output Setting.
Query returns an actual output status.
Parameter
0|1, OFF|ON
Query
OUTPut[:STATe]?
Return
<Bool> 0|1
OUTPut:ENA[:STATe] <Bool>
Function Enables / Disables the ENA function.
If disabled, power supply ignores the ENA pin signal (J1-10).
Parameter
0|1, OFF|ON
Query
OUTPut:ENA[:STATe]?
Return
<Bool> 0|1
OUTPut:ENA:POLarity <DSC>
Function Sets the ENA signal polarity.
NORM - (same as interlock) - Output ON if ENA pin signal (J1-10) is low
('0').
REV - Output ON if ENA pin signal (J1-10) is high ('1').
Parameter
0|1, REV|NORM
Query
OUTPut:ENA:POLarity?
Return
<DSC> REV|NORM
OUTPut:ILC[:STATe] <Bool>
Function Enables / Disables the ILC function.
If disabled, power supply ignores the ILC pin signal (J1-19).
Parameter
0|1, OFF|ON
Query
OUTPut:ILC[:STATe]?
Return
<Bool> 0|1
OUTPut:MODE?
Query Returns the power supply operation mode.
If power supply output is OFF, returns OFF.
If power supply output is ON, returns the CV for Constant Voltage, CC for
Constant Current, or CP for Constant Power Limit.
Return
<DSC> OFF|CV|CC|CP