Premier 24 Installation Manual Installation
INS248 29
Keypad zones do not operate
•
Each keypad zone has to be mapped onto the system
before it can be used (see page 51 for details)
• The zone is not programmed (see page 34 for details)
Keypad emergency keys do not operate
•
Each keypad can be configured so that the emergency
keys PA, FIRE and MEDICAL can be enabled or
disabled. Check that the keypad has been
programmed correctly (see page 51 for details)
Expander
Expander does not operate at all
•
Check that the expander is wired correctly from the
control panel (see page 13 for wiring details)
• Check the network PTC LED for faults
System does not recognise zones
•
If the expander is on a long cable run, check the
voltage between the + and – terminals at the expander
and ensure that it measures no less than 10.0V
The speaker output does not work
•
The expander can be configured so that Alarm, Entry,
Exit, Chime tones etc. can be enabled or disabled.
Check that the expander has been programmed
correctly (see page 53 for details)
• The speaker volume on the expander is electronically
adjustable. Check the volume is set to the desired level
(see page 53 for details)
Zones
One or more zones show an alarm
•
Check that the zone is wired correctly (see page 21 for
wiring details)
Digimodem
The Digimodem will not dial
•
By default the communicator is disabled, check that the
communicator is enabled (see page 64 for details)
• Check that the telephone line has been correctly wired
to the communicator (see page 25 for wiring details)
• Check that the telephone numbers are programmed
correctly (see page 63 for details)
• Check that the account numbers are programmed
correctly (see page 63 for details)
• Check that the dial attempts are not programmed as
zero (see page 63 for details)
• Check that the reporting options have been
programmed correctly (see page 63 for details)
Digimodem dials but does not communicate
•
Check that the telephone numbers are programmed
correctly (see page 63 for details)
• Check that the correct protocol is programmed (see
page 63 for details)
Operation
The system will not allow me to arm
•
Check that there are no outstanding problems (see
page 30 for details)
• Check that there are no outstanding alarms that require
resetting (see page 30 for details)
• Check that the User code has been programmed to
allow arming (see page 75 for details)
The system will not allow me to disarm
•
Check that the User code has been programmed to
allow disarming (see page 75 for details)