148
148
NV10P - Manual - 01 - 2015
APPENDIX
Description Parameter Unit Setting range
Binary input IN30
IN30
Logic
Active-ON | Active-OFF
IN30 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN30 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN30 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN30 matching (B)
none
Binary input IN31
IN31
Logic
Active-ON | Active-OFF
IN31 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN31 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN31 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN31 matching (B)
none
Binary input IN32
IN32
Logic
Active-ON | Active-OFF
IN32 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN32 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN32 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN32 matching (B)
none
Binary input IN33
IN33
Logic
Active-ON | Active-OFF
IN33 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN33 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1