156
156
NV10P - Manual - 01 - 2015
APPENDIX
Description Parameter Unit Setting range
Th>8 Breaker failure Th>8BF
OFF | ON
Th>8 Trip relays Th>8-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>8 Trip LEDs Th>8-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Diagnostic
PT100 probe diagnostic relays PT100Diag-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
PT100 probe diagnostic LEDs PT100Diag-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Undervoltage - 27
Common confi guration
27 Operating logic Logic27
OR | AND
U< Element
Setpoints
U< Enable U< Enable
OFF | ON
U< Curve type U<Curve
INVERSE | DEFINITE
U< Logical block U<BLK1
OFF | ON
U< Breaker failure U<BF
OFF | ON
U< Disabling by CB_OPEN
U<disbyCB_
OPEN
OFF | ON
U< Start relays U<ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U< Trip relays U<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U< Start LEDs U<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
U< Trip LEDs U<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
27 First threshold defi nite time
State
OFF | ON
Pickup value
Un 0.05 ... 1.10 step = 0.01
U<def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
27 First threshold inverse time
State
OFF | ON
Pickup value
Un 0.05 ... 1.10 step = 0.01
U<inv Operating time tU<inv s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
U<< Element
Setpoints
U<< Logical block U<<BLK1
OFF | ON
U<< Breaker failure U<<BF
OFF | ON
U< Disabling by U<< start U<disbyU<<
OFF | ON
U<< Disabling by CB_OPEN
U<<disbyCB_
OPEN
OFF | ON
U<< Start relays U<<ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U<< Trip relays U<<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U<< Start LEDs U<<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
U<< Trip LEDs U<<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
27 Second threshold defi nite time
State
OFF | ON
Pickup value
Un 0.05 ... 1.10 step = 0.01

Table of Contents