APPENDIX
Description Parameter Unit Setting range
UE> Disabling by CB_OPEN
UE>disbyCB_
OPEN
OFF | ON
UE> Start relays UE>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Trip relays UE>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Start LEDs UE>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
UE> Trip LEDs UE>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
59N First threshold defi nite time
State
OFF | ON
Pickup value
UEn 0.01 ... 0.70 step = 0.01
UE>def Operating time
Value
s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
59N First threshold inverse time
State
OFF | ON
Pickup value
UEn 0.01 ... 0.50 step = 0.01
UE>inv Operating time tUE>inv s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE>> Element
Setpoints
UE>> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE>> Logical block UE>>BLK1
OFF | ON
UE>> Enable UE>>BF
OFF | ON
UE> Disabling by UE>> start UE>disbyUE>>
OFF | ON
UE>> Disabling by CB_OPEN
UE>>disbyCB_
OPEN
OFF | ON
UE>> Start relays UE>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE>> Trip relays UE>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE>> Start LEDs UE>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
UE>> Trip LEDs UE>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
59N Second threshold defi nite time
State
OFF | ON
Pickup value
UEn 0.01 ... 0.70 step = 0.01
UE>>def Operating time
Value
s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE>>def Enable shrink time EnTc UE>>def
OFF | ON
UE>> Shrink time tcUE>>def s 0.07 ... 10.00 step = 0.01
tcUE>>def Activation time
Value
s 1 ... 60 step = 1
Negative sequence overvoltage - 59V2
U2> Element
Setpoints
U2> Logical block U2>BLK1
OFF | ON
U2> Breaker failure U2>BF
OFF | ON
U2> Disabling by CB_OPEN
U2>disbyCB_
OPEN
OFF | ON