161
NV10P - Manual - 01 - 2015
APPENDIX
Description Parameter Unit Setting range
f>> Start relays f>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f>> Trip relays f>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f>> Start LEDs f>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f>> Trip LEDs f>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81O Second threshold defi nite time
State
OFF | ON
Pickup value
fn 1.000 ... 1.200 step = 0.001
f>>def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
f>>def Enable shrink time EnTc f>>def
OFF | ON
f>> Shrink time tcf>>def s 0.07 ... 10.00 step = 0.01
tcf>>def Activation time
Value
s 1 ... 60 step = 1
Underfrequency - 81U
f< Element
Setpoints
f< Logical block f<BLK1
OFF | ON
f< Breaker failure f<BF
OFF | ON
f< Disabling by CB_OPEN
f<disbyCB_
OPEN
OFF | ON
f< Start relays f<ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f< Trip relays f<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f< Start LEDs f<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f< Trip LEDs f<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81U First threshold defi nite time
State
OFF | ON
Pickup value
fn 0.800 ... 1.000 step = 0.001
f<def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Voltage control
f< Control enable f<&
OFF | ON
f< Controlled by UE>> f<&UE>>
OFF | ON
f< Controlled by digital input f<&DIGIN
OFF | ON
f< Controlled by 27V1 f<&27V1
OFF | ON
f< Controlled by 59V2 f<&59V2
OFF | ON
f< Controlled by U< f<&U<
OFF | ON
f< Controlled by 61850 network no link
f<&rete61850-
KO
OFF | ON
f<& Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 200.0 step = 0.1
f< Control relays f<&-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f< Control LEDs f<&-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f<< Element
Setpoints
f<< Logical block f<<BLK1
OFF | ON