162
162
NV10P - Manual - 01 - 2015
APPENDIX
Description Parameter Unit Setting range
f<< Breaker failure f<<BF
OFF | ON
f< Disabling by f<< start f<disbyf<<
OFF | ON
f<< Disabling by CB_OPEN
f<<disbyCB_
OPEN
OFF | ON
f<< Start relays f<<ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f<< Trip relays f<<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f<< Start LEDs f<<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f<< Trip LEDs f<<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81U Second threshold defi nite time
State
OFF | ON
Pickup value
fn 0.800 ... 1.000 step = 0.001
f<<def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
f<<def Enable shrink time EnTc f<<def
OFF | ON
f<< Shrink time tcf<<def s 0.07 ... 10.00 step = 0.01
tcf<<def Activation time
Value
s 1 ... 60 step = 1
f<<< Element
Setpoints
f<<< Logical block f<<<BLK1
OFF | ON
f<<< Breaker failure f<<<BF
OFF | ON
f< Disabling by f<<< start f<disbyf<<<
OFF | ON
f<< Disabling by f<<< start f<<disbyf<<<
OFF | ON
f<<< Disabling by CB_OPEN
f<<<disbyCB_
OPEN
OFF | ON
f<<< Start relays f<<<ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f<<< Trip relays f<<<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f<<< Start LEDs f<<<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f<<< Trip LEDs f<<<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81U Third threshold defi nite time
State
OFF | ON
Pickup value
fn 0.800 ... 1.000 step = 0.001
f<<<def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
f<<<< Element
Setpoints
f<<<< Logical block f<<<<BLK1
OFF | ON
f<<<< Breaker failure f<<<<BF
OFF | ON
f< Disabling by f<<<< start f<disbyf<<<<
OFF | ON
f<< Disabling by f<<<< start f<<disbyf<<<<
OFF | ON
f<<< Disabling by f<<<< start f<<<disbyf<<<<
OFF | ON
f<<<< Disabling by CB_OPEN
f<<<<disbyCB_
OPEN
OFF | ON
f<<<< Start relays f<<<<ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f<<<< Trip relays f<<<<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10