Description Parameter Unit Setting range
f<<<< Start LEDs f<<<<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f<<<< Trip LEDs f<<<<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81U Fourth threshold defi nite time
State
OFF | ON
Pickup value
fn 0.800 ... 1.000 step = 0.001
f<<<<def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Frequency rate of change - 81R
df> Element
Setpoints
df> Operating mode Mode-df>
Module | Positive | Negative
df> Logical block df>BLK1
OFF | ON
df> Breaker failure df>BF
OFF | ON
df> Disabling by CB_OPEN
df>disbyCB_
OPEN
OFF | ON
df> Start relays df>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
df> Trip relays df>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
df> Start LEDs df>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
df> Trip LEDs df>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81R First threshold defi nite time
State
OFF | ON
Pickup value
Hz/s 0.1 ... 10.0 step = 0.1
df>def Operating time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
df>> Element
Setpoints
df>> Operating mode Mode-df>>
Module | Positive | Negative
df>> Logical block df>>BLK1
OFF | ON
df>> Breaker failure df>>BF
OFF | ON
df> Disabling by df>> start df>disbydf>>
OFF | ON
df>> Disabling by CB_OPEN
df>>disbyCB_
OPEN
OFF | ON
df>> Start relays df>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
df>> Trip relays df>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
df>> Start LEDs df>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
df>> Trip LEDs df>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81R Second threshold defi nite time
State
OFF | ON
Pickup value
Hz/s 0.1 ... 10.0 step = 0.1
df>>def Operating time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
df>>> Element
Setpoints