164
164
NV10P - Manual - 01 - 2015
APPENDIX
Description Parameter Unit Setting range
df>>> Operating mode Mode-df>>>
Module | Positive | Negative
df>>> Logical block df>>>BLK1
OFF | ON
df>>> Breaker failure df>>>BF
OFF | ON
df> Disabling by df>>> start df>disbydf>>>
OFF | ON
df>> Disabling by df>>> start df>>disbydf>>>
OFF | ON
df>>> Disabling by CB_OPEN
df>>>disbyCB_
OPEN
OFF | ON
df>>> Start relays df>>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
df>>> Trip relays df>>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
df>>> Start LEDs df>>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
df>>> Trip LEDs df>>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81R Third threshold defi nite time
State
OFF | ON
Pickup value
Hz/s 0.1 ... 10.0 step = 0.1
df>>>def Operating time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
df>>>> Element
Setpoints
df>>>> Operating mode Mode-df>>>>
Module | Positive | Negative
df>>>> Logical block df>>>>BLK1
OFF | ON
df>>>> Breaker failure df>>>>BF
OFF | ON
df> Disabling by df>>>> start df>disbydf>>>>
OFF | ON
df>> Disabling by df>>>> start df>>disbydf>>>>
OFF | ON
df>>> Disabling by df>>>> start
OFF | ON
df>>>> Disabling by CB_OPEN
df>>>>disbyCB_
OPEN
OFF | ON
df>>>> Start relays df>>>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
df>>>> Trip relays df>>>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
df>>>> Start LEDs df>>>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
df>>>> Trip LEDs df>>>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81R Fourth threshold defi nite time
State
OFF | ON
Pickup value
Hz/s 0.1 ... 10.0 step = 0.1
df>>>>def Operating time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Trip circuit supervision - 74TCS
74TCS Enable 74TCS Enable
OFF | ON
74TCS Logical block 74TCS-BLK1
OFF | ON
74TCS Start relays 74TCS-ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
74TCS Trip relays 74TCS-TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
74TCS Start LEDs 74TCS-ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
74TCS Trip LEDs 74TCS-TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Breaker failure - BF
BF Enable BF Enable
OFF | ON

Table of Contents