Troubleshooting
Should main power be lost to the mill when the control power circuit is on, the control power circuit
turns o and stays o unl power is restored and the green Start buon is pressed.
This prevents the mill from restarng without operator acon aer any power outage, natural or
man-made. Transformer XFM1 reduces the incoming voltage from a nominal 230 (or 220) VAC to a
nominal 115 (or 110) VAC. 115 V control circuits are industry standard in North America (this allows
the use of readily available push buons, contactors, and other control circuit components).
If your wall breaker consistently trips whenever you power on the spindle, you should verify that
mill power is not coming through a ground fault interrupter (GFI, or RCCB in Europe). The lters in
the spindle drive can allow minor current leakage to ground that, while considered safe, may also
be sucient to trip a normal GFI.
10.5.3 Controller Communication Subsystem
10.5.3.1 Overview
PathPilot is the operang system for the PCNC mill. It allows for manual jogging of the X- ,Y- ,Z- , and
A-axis, spindle speed, and the coolant pump through the PathPilot interface. It also allows the mill
to run automacally with operator supplied programs. PathPilot communicates with the control
board to provide mill control. The controller LED on the Operator Panel must be illuminated before
the controller can control the mill.
10.5.3.2 Details on Controller Communication Subsystem
The operang system allows the operator to jog or posion the X-, Y-, Z-, and A-axis and to control
the spindle speed and coolant pump operaon by use of the keyboard, mouse, and the jog shule.
The operang system also accepts G-code programs that automacally control the mill.
The controller’s interface port communicates with the control board via a printer cable which has a
DB-25 connector on each end. In order for the controller to control the mill, the PathPilot operang
system must be running, the Machine LED must be on, and communicaon must be established
between the controller and the control board. Communicaon is established by clicking the Reset
buon on the screen. This causes the Reset buon to stop blinking and also powers on the controller
LED on the mill Operator Panel. Once communicaon is established, the PathPilot controller can
control mill operaon (see Figure 10.7).