GX9 ASD Installation and Operation Manual 107
VI/II Reference Point 2
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the VI/II terminal when the
VI/II terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.
This parameter sets the VI/II level that is associated with VI/II Input Point 2
Frequency when operating in the Speed control mode or is associated with the
VI/II Input Point 1 Torque when operating in the Torque Control mode.
This value is entered as 0% to 100% of the VI/II signal range.
See VI/II Reference Point 1 (F201) for more information on this setting when
used for Speed control.
See VI/II Input Point 1 Torque (F205) for more information on this setting
when used for Torque Control.
Direct Access Number — F203
Parameter Type — Numerical
Factory Default 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
VI/II Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the VI/II terminal when the
VI/II terminal is used as the control input while operating in the Speed Control
mode.
This parameter sets VI/II Input Point 2 Frequency and is the frequency that is
associated with the setting of VI/II Reference Point 2 when operating in the
Speed Control mode.
See VI/II Reference Point 1 (F201) for more information on this setting.
Direct Access Number — F204
Parameter Type — Numerical
Factory Default 66.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F203 F204