192 GX9 ASD Installation and Operation Manual
Upper Limit Frequency Adjustment
Program Terminal Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Upper Limit. When enabled, either VI/II or RR may be used
as an input source for the modification of the Upper Limit setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F651
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Acceleration Time Adjustment
Program Terminal Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Acceleration Time. Selecting either VI/II or RR enables this
feature. The selected input is used as a multiplier of the programmed
Acceleration Time setting. The multiplication factor may be from 1 to 10.
Note: An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F652
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Deceleration Time Adjustment
Program Terminal Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Deceleration Time. Selecting either VI/II or RR enables this
feature. The selected input is used as a modifier of the programmed
Deceleration Time setting.
Note: A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F653
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Torque Boost Adjustment
Program Terminal Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Torque Boost setting. Selecting either VI/II or RR enables
this feature. The selected input is used as a modifier of the programmed Torque
Boost setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F654
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F651 F654