GX9 ASD Installation and Operation Manual 193
Adding Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — CN8 Option
6 — Binary/BCD (Option)
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Option Board
10 — UP/DOWN Frequency
11 — Pulse Input (Option)
Direct Access Number — F660
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Multiplying Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the commanded frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the commanded frequency.
If Setting (F729) is selected, the % value entered at parameter F729 is used as
the multiplier of the commanded frequency.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F729)
Direct Access Number — F661
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F660 F661