40 GX9 ASD Installation and Operation Manual
EOI Command (RS232/RS485) Menu
The Command (RS232/RS485) menu is accessed by pressing ESC from the Frequency Command
screen. The control settings of the Command (RS232/RS485) menu are effective for EOI control only.
The Command (RS232/RS485) menu provides quick access to the following menu parameters:
DirectionForward or Reverse.
Stop Pattern — The Decel Stop or Coast Stop settings determines the method used to stop the motor
when using the Stop|Reset key of the EOI. The Decel Stop setting enables the Dynamic Braking
system setup at F304 or the DC Injection Braking system setup at F250, F251, and F252. The Coast
Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Note: The Stop Pattern setting has no effect on the Emergency Off settings of F603.
V/f Group — 1 of 4 V/f profiles may be selected and run. Each V/f profile is comprised of 4 user
settings: Base Frequency, Base Frequency Voltage, Manual Torque Boost, and Motor Overload
Protection. Expanded descriptions of these parameters may be found in the section titled Direct
Access Parameter Information on pg. 75.
Accel/Decel Group — 1 of 4 Accel/Decel profiles may be selected and run. Each of the Accel/Decel
profiles is comprised of 3 user settings: Acceleration, Deceleration, and Pattern. Expanded
descriptions of these parameters may be found in the section titled Direct Access Parameter
Information on pg. 75.
PID Control — This feature enables or disables the PID
feedback function.
Torque Limit Group — This parameter is used to select 1 of 4 preset positive torque limits to apply
to the active motor (of a multiple motor configuration). The settings of profiles 1 – 4 may be setup at
F441, F444, F446, and F448, respectively.
VLP Technology Control — This feature enables or disables the Virtual Linear Pump function.